MODEL 5096N : Real-Time Data Transmitter
(NEMA Enclosure)
General Description:
The Model 5096 Real-Time Data Transmitter collects, processes, and transmits analog
and digital sensor data on events and timed intervals. The collection, processing,
and transmission of sensor data is controlled by parameters that are easily programmed
using a terminal or computer with standard communications software. Communications
with the transmitter is through an RS-232 port.
The Model 5096 Data Transmitter features on-board data logging capabilities. Data
is stored automatically in memory as backup to radio transmission or as a stand-alone
data logger. The 24K memory capacity can store up to 4,000 event data points or more
than 12,000 data points at uniform time intervals. Data can be downloaded using a
portable computer during onsite visits.
The Model 5096 Data Transmitter is field-programmable, including a full set of commands
for sensor setup and data logging. You can set and read sensors, access on-line help,
and perform diagnostics at the remote site. Sensor parameters can be individually
set, including transmission intervals, sample intervals, and starting values. Sensor
data can be calibrated to report in engineering units. For firmware Versions 3.1
and later, no programming is required with default program setup for standard sensors.
The Model 5096 Data Transmitter logic board has up to 4 digital inputs, 7 analog
inputs, and 8 digital status lines for a wide variety of sensor configurations. The
battery voltage can be set to transmit at selected time intervals. Each sensor’s
default identification number is based on the setting of the 4 digit ID switch. Each
sensor ID number can be programmed to any other unused number between 0 and 8191.
The programmable ID feature helps avoid ID overlap when adding additional transmitters
to an existing ALERT system.
The Model 5096 Data Transmitter includes a TEST button, LED indicators, and test
points for diagnostic testing. The TEST function checks memory, both RAM and ROM,
clock functions, and sensor values. Active sensors are read and their values are transmitted.
The Model 5096N is housed in a NEMA-4X fiberglass enclosure and is designed for outdoor
mounting onto a panel or a mast as well as indoor wall-mounting. The 5096N can be
equipped with a radio and used as part of a telemetry system, or it can be used as
a stand alone data logger. |
|
|
 |
 |
 |
|
|
MODEL 5096 : SPECIFICATIONS
- Environment
- Operating temperature: -40 to 65 °C
- Storage temperature: -60 to 75 °C
- Operating humidity: 0 to 100% RH, non-condensing
- Main Logic Board
- Memory size: 96 Kbytes, CMOS EPROM - 64 Kb,
- CMOS RAM - 32 Kb, battery backed
- Manual controls: Reset switch, Test switch, Station ID
- Diagnostic LEDS: Test error, power error, sensor power, TX-on,
- test, run
- Standby current: <300 µA (120 µA)
- Supply voltage: 10.5 to 18.5 Vdc (12.2 to 14.5 Vdc battery
- operated with radio)
- Serial port baud rate: 300 (default), 1200, 2400, 4600, 9600
- Transmitter baud rate: 300
- CPU type: 80C196 (5MHz)
- Clock: Real-time software clock
- Digital inputs: 4 digital channels ,up to 100 event triggers/second,
- 2 channels up/ down accumulator,
- 2 channels up only with pre-divide counter.
- Status inputs: 1 channel with 8 digital status lines.
- Analog inputs: 8 analog ch. (10-bit resolution with ± 0.24%
- non-linearity error), 7 ch. (0-5 Vdc),
- 1 chn. for battery voltage.
- Analog supply voltages: Vbatt (12 Vdc nominal) non-switched,
- +5 Vdc non-switched, Vsw (12 Vdc nominal) switched,
- Vref (+5 Vdc) switched
- Model 5096N
- Enclosure: NEMA-4X fiberglass
- Size: 13.6 in. x 11.5 in. 5.3 in.
- Mounting holes: 12.75 in. x 8 in.
- Weight: 16 lbs with battery
- Shipping weight: 12 lbs (battery shipped separately)
- Sensor inputs: Enclosure with 7 cable strain reliefs
- Connections: Screw terminal interconnect PCB for
- 4 digital, 7 analog, and 8 digital status
- or MS connector package
- Battery: 12 Vdc, 7 Amp-hour rechargeable gel cell
- Antenna: N-type female lightning arrestor
- External 12 Vdc connector: 3 pin MS male connector for 12 Vdc input
- Serial console: 9 pin D-type RS232C Female connector
- mounted on circuit board
|
|
|
 |
 |
|
|
MODEL 5096 : OPTIONS
- RTR: Radio Link (Specify frequency)
- 5096STATUS: 10 pin MS Female Bulkhead Connector
- 5096RS232: 7 pin MS Male Bulkhead Connector
- 9601-xx-Vyy: Firmware Upgrade (Specify model and version)
|
|
|
 |
|
 |
|
|
|
|
|
|
|
|
|
5096N
Transmitter in NEMA 4X Enclosure |
|
|
 |
 |
|
|
|
|
|
|
|
|
|
ADOBE PDF
|
|
|
FILE SIZE: |
310KB |
|
|
 |
 |
|
|
|
|
|
|
|
|
|
ADOBE PDF
|
|
|
FILE SIZE: |
1766KB |
|
|
 |
 |
|
|
|
: FIRMWARE ENHANCEMENTS : |
|
|
|
|
|
|
|
ADOBE PDF
|
|
|
FILE SIZE: |
222KB |
|
|
 |
|